How to Set E.S.P?
22 Indoor Unit
How to Set E.S.P?
Note: 1. The above table shows the correlation between the air rates and E.S.P.
2. Make sure to check and adjust E.S.P (external static pressure) value after the installa-
tion of the product. Otherwise, there is a risk of weak cooling/heating and condensed
water discharge/drop.
ARNU07GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU09GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU12GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU15GB3G4+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU18GB4G4+PBSGB40(Acc'y), PBSC40(Acc'y)
ARNU24GB4G4+PBSGB40(Acc'y), PBSC40(Acc'y)
0(0) 1(10) 2(20) 3(30) 4(40)
60 6.29 3.03 0.93 - -
65 6.61 4.84 1.52 - -
70 7.69 5.64 2.18 0.79 -
75 8.19 6.28 2.81 0.85 -
80 8.91 7.43 4.96 1.58 -
85 9.51 8.14 5.91 2.75 0.95
90 10.21 8.76 6.79 3.41 1.36
95 10.83 9.62 8.11 5.48 2.61
100 11.31 10.55 9.02 6.12 3.31
105 11.84 11.19 9.99 8.28 5.32
110 12.68 11.88 10.38 9.16 6.92
115 13.19 12.22 11.55 10.21 8.23
0(0) 1(10) 2(20) 3(30) 4(40)
75 10.32 7.68 3.55 - -
80 11.06 8.77 4.71 1.38 -
85 11.84 10.02 6.95 2.16 -
90 12.73 10.74 8.26 4.73 1.25
95 13.47 12.13 9.93 6.74 2.73
100 14.16 13.25 10.51 8.41 3.65
105 15.29 14.11 12.31 9.83 6.21
110 16.09 14.77 13.49 10.39 8.32
115 16.91 15.88 14.48 12.77 9.92
120 17.81 16.88 15.15 13.98 10.85
125 18.55 17.84 16.12 15.13 12.97
130 19.01 18.55 17.33 16.28 14.59
(Unit: CMM)
(Unit: CMM)
Static Pressure(mmAq(Pa))
Setting Value
Static Pressure(mmAq(Pa))
Setting Value
Page view 21