Operation & Maintenance ManualLGMODELS: RCAW - Compact (50Hz)website http://www.lgservice.comIMPORTANT• Please read this Operation & Maintenan
Safety Considerations10 Chiller Air-cooled ScrewConsult a water treatment specialist for propertreatment procedures.• Hard scale may require chemical
GeneralOperation & Maintenance Manual 11GENERALThis manual is composed of information on control, operation, start-up, service and troubleshootin
General12 Chiller Air-cooled ScrewMain MenuThe main menu is composed of 4 screen cuts. Moving among them is accomplished by the manipulation of the ar
GeneralOperation & Maintenance Manual 13User Setting The user setting is composed of 8 screen cuts. Moving among them is accomplished by the mani
General14 Chiller Air-cooled ScrewCompressor shutdown temperature means the temperature where the compressor must be shut downed by low temper-ature.
GeneralOperation & Maintenance Manual 15The I/O display is composed of 9 screen cuts. Through the I/O Display, switch status of signal inputs to
General16 Chiller Air-cooled ScrewThe liquid flow switch detects chilled water flow, and the water flow must build during running the chiller. The ope
GeneralOperation & Maintenance Manual 17Alarm DisplayThrough the alarm display, recent 10 alarms are displayed with their invocation time. The al
General18 Chiller Air-cooled ScrewSystem SettingThe system setting is composed of 2 screen cuts. Through the system setting, the temperature readings
GeneralOperation & Maintenance Manual 19Parameter SettingFig. 7Par. SettingSystem SettingDelay SettingContentFan Start Temp3Fan Start Temp2Fan St
2 Chiller Air-cooled ScrewSAFETY CONSIDERATIONSWarning...
General20 Chiller Air-cooled ScrewDelay SettingFig. 8Delay SettingPar. SettingAlarm Display ContentTemp AlarmSystem OilWater FlowSystem PressureStart
ControlsOperation & Maintenance Manual 21 PLC and HMI UnitPLC and HMI UnitCONTROLSThe HMI (Human Machine Interface) side of the PLC (Programmabl
Controls22 Chiller Air-cooled ScrewAmong the menu items, some items are protected from access with authorization code system. The user setting is pro-
ControlsOperation & Maintenance Manual 23The back side of the PLC and HMI assembly is shown in the below picture. The PLC is composed of base boa
Controls24 Chiller Air-cooled ScrewOn the top side of the PLC, DIP switches and indicating LEDs are installed. Normally, the D2 LED has to blink with
ControlsOperation & Maintenance Manual 25Actual locations of the connectors are shown in the above pictures and detail descriptions of the connec
Controls26 Chiller Air-cooled ScrewConnector PinDescriptionWire No.CN1(POW)AC1AC2FGO012627717224VDC-PositiveCN2(DO-1)O02O03O04O05O06O07O08COM737475767
ControlsOperation & Maintenance Manual 27Connector PinDescriptionWire No.CN4(DI -1)I01 31Remote ControlI02 32 System Oil PressureI03 33I04 34I05
Controls28 Chiller Air-cooled ScrewConnector MODBUSPinDescriptionRX2/D2+TX2/D2-Wire No.MODBUS on RS-485: D+MODBUS on RS-485: D-CN6(RTDI)RTD1+RTD1-RTD1
ControlsOperation & Maintenance Manual 29The MODBUS address map of registers is shown in the below table.MODBUS Address Meaning Indicating UnitNO
Safety ConsiderationsOperation & Maintenance Manual 3Installing, starting up, and servicing this equipment can be hazardous due to system pressur
Controls30 Chiller Air-cooled Screw Machine On/off ControlThere are two modes to turn on/off the machine. One is the Hand Mode and the other is the A
Start-upOperation & Maintenance Manual 31 Pre Start-UpDo not attempt to start the chiller until the following checks have been completed.• Check
Start-up32 Chiller Air-cooled ScrewDo not manually operate contactors. Serious damage to the machine may result. The following procedureshould be foll
Start-upOperation & Maintenance Manual 33After the above procedure, allow unit to operate and confirm that everything is functional properly. Che
Start-up34 Chiller Air-cooled ScrewTemperatureVoltageTemperatureTemperature limits during the operation of the unit are as follows.Maximum ambient tem
Start-upOperation & Maintenance Manual 35Flow RateThe basic flow rate of the chiller must follow the values of the table showing the maximum, min
Start-up36 Chiller Air-cooled Screwn Compact Fig. 15Note: For flow out of this range, consult LG.* : P – 380V, Q - 400V, R - 415V02040608010012014016
OPERATION Sequence of OperationThe sequence of the operation is depicted by the flow chart in the below. When the start is in effect, the condenser f
Operation38 Chiller Air-cooled ScrewCondenserFan=ONWater Pump= ONAlarmY Start: M4 : M1=ON & M3=ON: Oil Heater=OFF: Oil Solenoid Valve(SV1)=ON: Tem
OperationOperation & Maintenance Manual 39Fig. 17MV2=OFF & MV3=OFFMV1=ON, SV2=OFFM2 =OFF & M1=OFFSV1=OFFWater Pump=OFFFan = OFF4-10MinYe
Safety Considerations4 Chiller Air-cooled ScrewFor re-installation of the installed product,always contact a dealer or an AuthorizedService Center.• T
Operation40 Chiller Air-cooled ScrewDelay control for the chiller is summarized in the below picture. There are two essential delays, stop to startdel
OperationOperation & Maintenance Manual 41Fig. 19Table 11CONTROL POINT DEFAULT RANGET1 34 30 ~ 34T2 39 35 ~ 39 T3 44 40 ~ 45T4 - -T5 - -100RT
Operation42 Chiller Air-cooled ScrewTo monitor the inlet water temperature, outlet water temperature, discharge temperature of the compressor,ambient
ServiceOperation & Maintenance Manual 43 Cycle ComponentsThe structure of the air-cooled cooling cycle is shown in the below. The unit is equipp
Service44 Chiller Air-cooled ScrewAs shown in the below, during rotation of the rotors the meshing shifts from the suction side to the dischargeside.
ServiceOperation & Maintenance Manual 45This means the displacement of refrigerant gas also increases, as a result the refrigeration capacity als
Service46 Chiller Air-cooled ScrewThe bearings used in the compressor required a small but steady quantity of oil for lubrication; the oil injectionin
ServiceOperation & Maintenance Manual 47In order to protect the compressor, the compressor has been installed three PTC temperature sensors insid
Service48 Chiller Air-cooled Screw Maintenance and cleaning of condenser coilPeriodically cleaning the surface of the coil is essential in maintainin
ServiceOperation & Maintenance Manual 49 Condenser fanThe fan motor and the fan must be fixated firmly on the top plate of the condenser with th
Safety ConsiderationsOperation & Maintenance Manual 5Do not damage or use an unspecified powercord.• There is risk of fire, electric shock, explo
Service50 Chiller Air-cooled ScrewCooler Flow SwitchFlow Switch is installed on the water outlet nozzle for all units as factory setting. The followi
ServiceOperation & Maintenance Manual 51 Dual Pressure Switch Differential Pressure SwitchDifferential pressure switch is also used for checkin
Service52 Chiller Air-cooled Screw Anti-freezing SwitchThe anti-freezing switch is used to detect too low water temperature. The switch is normally c
ServiceOperation & Maintenance Manual 53Refrigerant Cycle Leakage testAs described in the installation manual, the unit is sufficiently charged
Service54 Chiller Air-cooled Screw Oil FilterThe oil filter is installed on the oil separator in oil return line to the compressor. Differential pres
ServiceOperation & Maintenance Manual 55 Oil Heater Solenoid ValveOne of the Solenoid Valve is installed between the Flash Gas Tank where the o
Service56 Chiller Air-cooled Screw Control SystemThe structures of the power panel and control panel are shown in the below. The power panel in the l
ServiceOperation & Maintenance Manual 57Power PanelOn the left side of the power panel, terminal blocks for main power connection are prepared. T
Service58 Chiller Air-cooled ScrewL1L3L21M2M1452361M1M2MSSS3LPVV=PLII=Wye Starting Delta RunningL1L3L21M2M1M1M2M2MSSS145263LPVV=PLIIx=3Fan contactor &
ServiceOperation & Maintenance Manual 59n Compressor OCR (Over Current Relay)The compressor OCR is thermal type and used to protect the compresso
Safety Considerations6 Chiller Air-cooled ScrewChanging the set value is prohibited.• Do not change the set value of the safety device.• If you opera
Service60 Chiller Air-cooled Screwn Voltage Monitoring Relay (5E) The voltage monitoring relay is used for the verification of proper power supply of
ServiceOperation & Maintenance Manual 61The voltage unbalance tripping is activated when the unbalance exceeds +5% more than 3 seconds. Similarly
Service62 Chiller Air-cooled Screw Assist RelayAssist Relay is the relay to check power supply of 220V to the controller. Assist Relay is as follows.
ServiceOperation & Maintenance Manual 63 Fan ContactorFan Contactor controls the start, stop and static range of the fan motor when the product
Service64 Chiller Air-cooled ScrewControl PanelOn the external door of the control panel there is emergency switch for the instant cutting out of cont
ServiceOperation & Maintenance Manual 65In the control panel, the PLC is installed as a central control station. The PLC is assembled with the HM
Service66 Chiller Air-cooled ScrewETC Temp. Sensor in Control BoxThis is used to detecting the temperature within the Control Box when operating the
ServiceOperation & Maintenance Manual 67 MaintenanceMaintenance ScheduleCheck Point Daily Monthly Every2 monthsEvery3 monthsEvery6 monthsEvery1
Trouble Shooting 68 Chiller Air-cooled ScrewIf a stoppage occurs more than once as a result of any of the safety devices, determine andcorrect the cau
Trouble Shooting Operation & Maintenance Manual 69SymptomUnit does not runCompressor operates toolong continuouslyPossible CausePossible RemedyCh
Safety ConsiderationsOperation & Maintenance Manual 7Do not leave refrigerant system open to air any longer than necessary. • Seal circuits being
Trouble Shooting 70 Chiller Air-cooled ScrewAlarmSpecific alarms, their recognition method, and their possible causes are listed here. To clear alarm
Trouble Shooting Operation & Maintenance Manual 71Displayed AlarmMessageRecognitionPossible CausePossible Remedy• Turn the emergency switchclockw
Displayed AlarmMessageRecognitionPossible CausePossible RemedyTrouble Shooting 72 Chiller Air-cooled Screw• Charge additional refrigerant• Test/Repair
Displayed AlarmMessageRecognitionPossible CausePossible RemedyTrouble Shooting Operation & Maintenance Manual 73• Review voltage • Repair or repl
Displayed AlarmMessageRecognitionPossible CausePossible RemedyTrouble Shooting 74 Chiller Air-cooled Screw• Charge additional refrigerant orreview val
Displayed AlarmMessageRecognitionPossible CausePossible RemedyTrouble Shooting Operation & Maintenance Manual 75FAN2B3B AlarmFAN4B5B AlarmExhaust
Appendix76 Chiller Air-cooled ScrewAppendix Wiring DiagramFig. 47SYMBOLFusesP/Box Heat dissipation fan LEGENDDESCRIPTIONAssist relayC/Box Heat dissip
AppendixOperation & Maintenance Manual 77Fig. 48SYMBOLFusesP/Box Heat dissipation fan LEGENDDESCRIPTIONAssist relayC/Box Heat dissipation fanOil
Appendix78 Chiller Air-cooled Screwn Cycle DiagramFig. 49DESCRIPTIONNoCompressor1Condensing coil2Receiver3Oil Filter4Oil separater 5Ejector for Oil Re
AppendixOperation & Maintenance Manual 79n Check List1. Project information2. Model informationChecklist for installation, and operationContents
Safety Considerations8 Chiller Air-cooled ScrewDo not use the chiller in special environments.• Oil, steam, sulfuric smoke, etc. can significantlyredu
Appendix80 Chiller Air-cooled Screw3. PRELIMINARY EQUIPMENT CHECK 4. Chilled Water System CheckCheckContentsNoYesDrain pipe is not clogged.NoYesInlet
AppendixOperation & Maintenance Manual 815. START-UP & OPERATIONAmbient air temperature%CCCCompressor capacitypsigCooler pressure droppsigRef
P/No.: MFL63291701Printed in KoreaAfter reading this manual, keep it in a place easily accessible to the user for future reference.
Safety ConsiderationsOperation & Maintenance Manual 9Be careful of disposal.• When disposing the device, request to the spe-cialized expert. Be