Operation & Maintenance Manual
LG
MODELS: RCAW - Compact (50Hz)
website http://www.lgservice.com
IMPORTANT
• Please read this Operation & Maintenance Manual
completely before Operating & Maintenance the product.
• Operating & Maintenance must be performed in
accordance with the national wiring standards by
authorized personnel only.
• Please retain this Operating & Maintenance for future
reference after reading it thoroughly.
R134a
Chiller
Air-cooled Screw
Page view 0
1 2 3 4 5 6 ... 81 82

Summary of Contents

Page 1 - Air-cooled Screw

Operation & Maintenance ManualLGMODELS: RCAW - Compact (50Hz)website http://www.lgservice.comIMPORTANT• Please read this Operation & Maintenan

Page 2 - TABLE OF CONTENTS

Safety Considerations10 Chiller Air-cooled ScrewConsult a water treatment specialist for propertreatment procedures.• Hard scale may require chemical

Page 3 - SAFETY CONSIDERATIONS

GeneralOperation & Maintenance Manual 11GENERALThis manual is composed of information on control, operation, start-up, service and troubleshootin

Page 4

General12 Chiller Air-cooled ScrewMain MenuThe main menu is composed of 4 screen cuts. Moving among them is accomplished by the manipulation of the ar

Page 5

GeneralOperation & Maintenance Manual 13User Setting The user setting is composed of 8 screen cuts. Moving among them is accomplished by the mani

Page 6

General14 Chiller Air-cooled ScrewCompressor shutdown temperature means the temperature where the compressor must be shut downed by low temper-ature.

Page 7

GeneralOperation & Maintenance Manual 15The I/O display is composed of 9 screen cuts. Through the I/O Display, switch status of signal inputs to

Page 8

General16 Chiller Air-cooled ScrewThe liquid flow switch detects chilled water flow, and the water flow must build during running the chiller. The ope

Page 9

GeneralOperation & Maintenance Manual 17Alarm DisplayThrough the alarm display, recent 10 alarms are displayed with their invocation time. The al

Page 10

General18 Chiller Air-cooled ScrewSystem SettingThe system setting is composed of 2 screen cuts. Through the system setting, the temperature readings

Page 11

GeneralOperation & Maintenance Manual 19Parameter SettingFig. 7Par. SettingSystem SettingDelay SettingContentFan Start Temp3Fan Start Temp2Fan St

Page 12 - Main Menu

2 Chiller Air-cooled ScrewSAFETY CONSIDERATIONSWarning...

Page 13 - User Setting

General20 Chiller Air-cooled ScrewDelay SettingFig. 8Delay SettingPar. SettingAlarm Display ContentTemp AlarmSystem OilWater FlowSystem PressureStart

Page 14 - 14 Chiller Air-cooled Screw

ControlsOperation & Maintenance Manual 21 PLC and HMI UnitPLC and HMI UnitCONTROLSThe HMI (Human Machine Interface) side of the PLC (Programmabl

Page 15 - I/O Display

Controls22 Chiller Air-cooled ScrewAmong the menu items, some items are protected from access with authorization code system. The user setting is pro-

Page 16 - 16 Chiller Air-cooled Screw

ControlsOperation & Maintenance Manual 23The back side of the PLC and HMI assembly is shown in the below picture. The PLC is composed of base boa

Page 17 - Alarm Display

Controls24 Chiller Air-cooled ScrewOn the top side of the PLC, DIP switches and indicating LEDs are installed. Normally, the D2 LED has to blink with

Page 18 - System Setting

ControlsOperation & Maintenance Manual 25Actual locations of the connectors are shown in the above pictures and detail descriptions of the connec

Page 19 - Parameter Setting

Controls26 Chiller Air-cooled ScrewConnector PinDescriptionWire No.CN1(POW)AC1AC2FGO012627717224VDC-PositiveCN2(DO-1)O02O03O04O05O06O07O08COM737475767

Page 20 - Delay Setting

ControlsOperation & Maintenance Manual 27Connector PinDescriptionWire No.CN4(DI -1)I01 31Remote ControlI02 32 System Oil PressureI03 33I04 34I05

Page 21 - CONTROLS

Controls28 Chiller Air-cooled ScrewConnector MODBUSPinDescriptionRX2/D2+TX2/D2-Wire No.MODBUS on RS-485: D+MODBUS on RS-485: D-CN6(RTDI)RTD1+RTD1-RTD1

Page 22 - 22 Chiller Air-cooled Screw

ControlsOperation & Maintenance Manual 29The MODBUS address map of registers is shown in the below table.MODBUS Address Meaning Indicating UnitNO

Page 23 - RTDI: CN6

Safety ConsiderationsOperation & Maintenance Manual 3Installing, starting up, and servicing this equipment can be hazardous due to system pressur

Page 24 - 24 Chiller Air-cooled Screw

Controls30 Chiller Air-cooled Screw Machine On/off ControlThere are two modes to turn on/off the machine. One is the Hand Mode and the other is the A

Page 25

Start-upOperation & Maintenance Manual 31 Pre Start-UpDo not attempt to start the chiller until the following checks have been completed.• Check

Page 26 - 26 Chiller Air-cooled Screw

Start-up32 Chiller Air-cooled ScrewDo not manually operate contactors. Serious damage to the machine may result. The following procedureshould be foll

Page 27

Start-upOperation & Maintenance Manual 33After the above procedure, allow unit to operate and confirm that everything is functional properly. Che

Page 28 - 28 Chiller Air-cooled Screw

Start-up34 Chiller Air-cooled ScrewTemperatureVoltageTemperatureTemperature limits during the operation of the unit are as follows.Maximum ambient tem

Page 29

Start-upOperation & Maintenance Manual 35Flow RateThe basic flow rate of the chiller must follow the values of the table showing the maximum, min

Page 30 - ■ Machine On/off Control

Start-up36 Chiller Air-cooled Screwn Compact Fig. 15Note: For flow out of this range, consult LG.* : P – 380V, Q - 400V, R - 415V02040608010012014016

Page 31 - START-UP

OPERATION Sequence of OperationThe sequence of the operation is depicted by the flow chart in the below. When the start is in effect, the condenser f

Page 32 - ■ Start-Up Procedure

Operation38 Chiller Air-cooled ScrewCondenserFan=ONWater Pump= ONAlarmY Start: M4 : M1=ON & M3=ON: Oil Heater=OFF: Oil Solenoid Valve(SV1)=ON: Tem

Page 33

OperationOperation & Maintenance Manual 39Fig. 17MV2=OFF & MV3=OFFMV1=ON, SV2=OFFM2 =OFF & M1=OFFSV1=OFFWater Pump=OFFFan = OFF4-10MinYe

Page 34 - ■ Operation Limits

Safety Considerations4 Chiller Air-cooled ScrewFor re-installation of the installed product,always contact a dealer or an AuthorizedService Center.• T

Page 35 - Flow Rate

Operation40 Chiller Air-cooled ScrewDelay control for the chiller is summarized in the below picture. There are two essential delays, stop to startdel

Page 36 - 36 Chiller Air-cooled Screw

OperationOperation & Maintenance Manual 41Fig. 19Table 11CONTROL POINT DEFAULT RANGET1 34 30 ~ 34T2 39 35 ~ 39 T3 44 40 ~ 45T4 - -T5 - -100RT

Page 37 - OPERATION

Operation42 Chiller Air-cooled ScrewTo monitor the inlet water temperature, outlet water temperature, discharge temperature of the compressor,ambient

Page 38 - 38 Chiller Air-cooled Screw

ServiceOperation & Maintenance Manual 43 Cycle ComponentsThe structure of the air-cooled cooling cycle is shown in the below. The unit is equipp

Page 39 - Stop logic

Service44 Chiller Air-cooled ScrewAs shown in the below, during rotation of the rotors the meshing shifts from the suction side to the dischargeside.

Page 40

ServiceOperation & Maintenance Manual 45This means the displacement of refrigerant gas also increases, as a result the refrigeration capacity als

Page 41

Service46 Chiller Air-cooled ScrewThe bearings used in the compressor required a small but steady quantity of oil for lubrication; the oil injectionin

Page 42 - ■ Sensors

ServiceOperation & Maintenance Manual 47In order to protect the compressor, the compressor has been installed three PTC temperature sensors insid

Page 43 - ■ Cycle Components

Service48 Chiller Air-cooled Screw Maintenance and cleaning of condenser coilPeriodically cleaning the surface of the coil is essential in maintainin

Page 44 - Table 14

ServiceOperation & Maintenance Manual 49 Condenser fanThe fan motor and the fan must be fixated firmly on the top plate of the condenser with th

Page 45

Safety ConsiderationsOperation & Maintenance Manual 5Do not damage or use an unspecified powercord.• There is risk of fire, electric shock, explo

Page 46 - Table 15

Service50 Chiller Air-cooled ScrewCooler Flow SwitchFlow Switch is installed on the water outlet nozzle for all units as factory setting. The followi

Page 47 - Table 16

ServiceOperation & Maintenance Manual 51 Dual Pressure Switch Differential Pressure SwitchDifferential pressure switch is also used for checkin

Page 48 - Condenser

Service52 Chiller Air-cooled Screw Anti-freezing SwitchThe anti-freezing switch is used to detect too low water temperature. The switch is normally c

Page 49 - ■ Condenser fan

ServiceOperation & Maintenance Manual 53Refrigerant Cycle Leakage testAs described in the installation manual, the unit is sufficiently charged

Page 50 - ■ Flow Switch

Service54 Chiller Air-cooled Screw Oil FilterThe oil filter is installed on the oil separator in oil return line to the compressor. Differential pres

Page 51 - ■ Dual Pressure Switch

ServiceOperation & Maintenance Manual 55 Oil Heater Solenoid ValveOne of the Solenoid Valve is installed between the Flash Gas Tank where the o

Page 52 - 52 Chiller Air-cooled Screw

Service56 Chiller Air-cooled Screw Control SystemThe structures of the power panel and control panel are shown in the below. The power panel in the l

Page 53 - ■ Charging the oil

ServiceOperation & Maintenance Manual 57Power PanelOn the left side of the power panel, terminal blocks for main power connection are prepared. T

Page 54 - ■ Oil Flow Switch

Service58 Chiller Air-cooled ScrewL1L3L21M2M1452361M1M2MSSS3LPVV=PLII=Wye Starting Delta RunningL1L3L21M2M1M1M2M2MSSS145263LPVV=PLIIx=3Fan contactor &

Page 55 - ■ Solenoid Valve

ServiceOperation & Maintenance Manual 59n Compressor OCR (Over Current Relay)The compressor OCR is thermal type and used to protect the compresso

Page 56 - ■ Control System

Safety Considerations6 Chiller Air-cooled ScrewChanging the set value is prohibited.• Do not change the set value of the safety device.• If you opera

Page 57 - Power Panel

Service60 Chiller Air-cooled Screwn Voltage Monitoring Relay (5E) The voltage monitoring relay is used for the verification of proper power supply of

Page 58 - 58 Chiller Air-cooled Screw

ServiceOperation & Maintenance Manual 61The voltage unbalance tripping is activated when the unbalance exceeds +5% more than 3 seconds. Similarly

Page 59 - Table 21

Service62 Chiller Air-cooled Screw Assist RelayAssist Relay is the relay to check power supply of 220V to the controller. Assist Relay is as follows.

Page 60 - 60 Chiller Air-cooled Screw

ServiceOperation & Maintenance Manual 63 Fan ContactorFan Contactor controls the start, stop and static range of the fan motor when the product

Page 61 - Table 22

Service64 Chiller Air-cooled ScrewControl PanelOn the external door of the control panel there is emergency switch for the instant cutting out of cont

Page 62 - ■ Compressor Contactor

ServiceOperation & Maintenance Manual 65In the control panel, the PLC is installed as a central control station. The PLC is assembled with the HM

Page 63 - ■ Fan Contactor

Service66 Chiller Air-cooled ScrewETC Temp. Sensor in Control BoxThis is used to detecting the temperature within the Control Box when operating the

Page 64 - Control Panel

ServiceOperation & Maintenance Manual 67 MaintenanceMaintenance ScheduleCheck Point Daily Monthly Every2 monthsEvery3 monthsEvery6 monthsEvery1

Page 65 - Power Supply

Trouble Shooting 68 Chiller Air-cooled ScrewIf a stoppage occurs more than once as a result of any of the safety devices, determine andcorrect the cau

Page 66 - ■ Ventilation Fan

Trouble Shooting Operation & Maintenance Manual 69SymptomUnit does not runCompressor operates toolong continuouslyPossible CausePossible RemedyCh

Page 67 - ■ Maintenance

Safety ConsiderationsOperation & Maintenance Manual 7Do not leave refrigerant system open to air any longer than necessary. • Seal circuits being

Page 68 - TROUBLE SHOOTING

Trouble Shooting 70 Chiller Air-cooled ScrewAlarmSpecific alarms, their recognition method, and their possible causes are listed here. To clear alarm

Page 69 - Trouble Shooting

Trouble Shooting Operation & Maintenance Manual 71Displayed AlarmMessageRecognitionPossible CausePossible Remedy• Turn the emergency switchclockw

Page 70 - 70 Chiller Air-cooled Screw

Displayed AlarmMessageRecognitionPossible CausePossible RemedyTrouble Shooting 72 Chiller Air-cooled Screw• Charge additional refrigerant• Test/Repair

Page 71

Displayed AlarmMessageRecognitionPossible CausePossible RemedyTrouble Shooting Operation & Maintenance Manual 73• Review voltage • Repair or repl

Page 72 - 72 Chiller Air-cooled Screw

Displayed AlarmMessageRecognitionPossible CausePossible RemedyTrouble Shooting 74 Chiller Air-cooled Screw• Charge additional refrigerant orreview val

Page 73

Displayed AlarmMessageRecognitionPossible CausePossible RemedyTrouble Shooting Operation & Maintenance Manual 75FAN2B3B AlarmFAN4B5B AlarmExhaust

Page 74 - 74 Chiller Air-cooled Screw

Appendix76 Chiller Air-cooled ScrewAppendix Wiring DiagramFig. 47SYMBOLFusesP/Box Heat dissipation fan LEGENDDESCRIPTIONAssist relayC/Box Heat dissip

Page 75

AppendixOperation & Maintenance Manual 77Fig. 48SYMBOLFusesP/Box Heat dissipation fan LEGENDDESCRIPTIONAssist relayC/Box Heat dissipation fanOil

Page 76 - Appendix

Appendix78 Chiller Air-cooled Screwn Cycle DiagramFig. 49DESCRIPTIONNoCompressor1Condensing coil2Receiver3Oil Filter4Oil separater 5Ejector for Oil Re

Page 77 - RCAW090PBAA

AppendixOperation & Maintenance Manual 79n Check List1. Project information2. Model informationChecklist for installation, and operationContents

Page 78 - RCAW090,100

Safety Considerations8 Chiller Air-cooled ScrewDo not use the chiller in special environments.• Oil, steam, sulfuric smoke, etc. can significantlyredu

Page 79 - 2. Model information

Appendix80 Chiller Air-cooled Screw3. PRELIMINARY EQUIPMENT CHECK 4. Chilled Water System CheckCheckContentsNoYesDrain pipe is not clogged.NoYesInlet

Page 80 - 4. Chilled Water System Check

AppendixOperation & Maintenance Manual 815. START-UP & OPERATIONAmbient air temperature%CCCCompressor capacitypsigCooler pressure droppsigRef

Page 81 - 5. START-UP & OPERATION

P/No.: MFL63291701Printed in KoreaAfter reading this manual, keep it in a place easily accessible to the user for future reference.

Page 82 - Printed in Korea

Safety ConsiderationsOperation & Maintenance Manual 9Be careful of disposal.• When disposing the device, request to the spe-cialized expert. Be