Installation of Outdoor Unit
• When installing the branch pipe, direction and angle of installation is not limited.
• Take care so that burrs and foreign material may not enter into the cutting surface when
connecting.
• Connect remaining those by cutting or direct insertion to the diameter of pipe.
Synchro Operation
Install the branch pipe so that pipe length and difference between high and low will not exceed
below Spec.
[Unit : m]
Branch
L1
H1
A
A
L2
L3
L4
L5
H2
Remote
Controller
Pipe Length & Height
Total(L1+L2+L3+L4+L5)
Main Pipe(L1)
Branch Pipe (L2+L3+L4+L5)
Each
Indoor-Outdoor (H1)
Indoor-Indoor (H2)
(L1+L2),(L1+L3),(L1+L4),(L1+L5)
A
Spec(MAX.)
80
45
40
15
30
1
70
10
Installation Manual 7
ENGLISH
Refrigerant Additional Charging Method
For additional charging method, see below table.
Indoor Unit Refrigerant Additional charging (g)
Duo
Trio
Quartet
Refrigerant = (L1-b) x B + (L2 + L3) x C
Refrigerant = (L1-b) x B + (L2 + L3 + L4) x C
Refrigerant = (L1-b) x B + (L2 + L3 + L4 + L5) x C
C
(g/m)
Pipe Diameter.
(mm)
Ø 6.35
Ø 9.52
35
40
b
(m)
Model
UU36WH/UU37WH
UU42WH/UU43WH
UU48WH/UU49WH
B
(g/m)
7.5 40
b : Rated performance for refrigerant line length.
C : Additional charging Refrigerant of Branch Liquid Pipe.
B : Additional charging Refrigerant of Main Liquid Pipe.
NOTICE
CAUTION:
• Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.