Installation
Installation Manual 7
ENGLISH
Installation
Indoor unit
Install the air conditioner in the location that sat-
isfies the following conditions.
• The place shall easily bear a load exceeding
four times the indoor unitʼs weight.
• The place shall be able to inspect the unit as
the figure.
• The place where the unit shall be leveled.
• The place shall easily connect with the outdoor
unit.
• The place where the unit is not affected by an
electrical noise.
• The place where air circulation in the room will
be good .
• There should not be any heat source or steam
near the unit
Confirm the positional relationship between the
unit and suspension bolts.
• Installation the ceiling opening to clean the fil-
ter or service under the product.
Inspection hole
(600 x 600)
Control box
H=20 or more
• Suitable dimension "H" is necessary to get a slope
to drain as shown in the figure
Side view
(unit: mm)
600
600
(Unit: mm)
Top view
Air outlet
Air outlet
A(Min)
Ceiling
Service Space
A
B
B(Min)
Selection of the best location
(Unit: mm)
Capacity (kBtu/h) A B
9 800 800
12/18 800 1000
24 800 1200