Installation
20 Outdoor Unit
When installing the branch pipe vertically between the outdoor units, the refrigerant can be uneven
between the outdoor units, leading to compressor burn and reduced capacity
2 Outdoor Units
1) For the high/low pressure common pipe, connect both
master outdoor unit and slave outdoor units to the pipe
by using elbows.
2) For cutting the pipe, connect the high/low pressure com-
mon pipe after removing burrs, dusts and foreign materi-
al within the pipe. Otherwise, the product may not oper-
ate due to sludge within the pipe.
3) For the working part leakage test, apply the nitrogen gas
pressure of 3.8MPa (38.7kgf/cm
2
).
4) The vacuum criteria is to maintain the vacuum level to
less than 5 Torr 1 hour after reaching 5 Torr. (Execute
the vacuum work again when it is below the criteria.)
5) Open the valve with the hexagon wrench.
* Install the branch pipe between outdoor units so
that the outlet pipe is parallel to the surface.
8. Connection of high/low pressure common pipe
9. Connecting branch pipe between outdoor units