Installation
20 Outdoor Unit
When installing the branch pipe vertically between the outdoor units, the refrigerant can be uneven
between the outdoor units, leading to compressor burn and reduced capacity
Slave
Outdoor Unit
Master
Outdoor Unit
2 Outdoor Units
1) For the high/low pressure common pipe, connect both
master outdoor unit and slave outdoor units to the pipe
by using elbows.
2) For cutting the pipe, connect the high/low pressure com-
mon pipe after removing burrs, dusts and foreign materi-
al within the pipe. Otherwise, the product may not oper-
ate due to sludge within the pipe.
3) For the working part leakage test, apply the nitrogen gas
pressure of 3.8MPa (38.7kgf/cm
2
).
4) The vacuum criteria is to maintain the vacuum level to
less than 5 Torr 1 hour after reaching 5 Torr. (Execute
the vacuum work again when it is below the criteria.)
5) Open the valve with the hexagon wrench.
* Install the branch pipe between outdoor units so
that the outlet pipe is parallel to the surface.
8. Connection of high/low pressure common pipe
9. Connecting branch pipe between outdoor units