P/NO : MFL67798033
INSTALLATION MANUAL
Original instruction
AIR
CONDITIONER
www.lg.com
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring standards by
authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.
[
Representative
]
LG Electronics Inc. EU Representative : LG Electronics European Shared Service Center B.V.
Krijgsman 1, 1186 DM Amstelveen, The Netherlands
[
Manufacturer
]
LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu, Changwon-si,
Gyeongsangnam-do, KOREA
For more information, Refer to the CD or LG Web site (www.lg.com).
ENGLISH
ITALIANO ESPAÑOL
FRANÇAIS
DEUTSCH
ČEŠTINA
ΕΛΛΗΝΙΚΆ
NEDERLANDS
POLSKI
LIMBA ROMÂNĂ
Page view 0
1 2 3 4 5 6 ... 28 29

Summary of Contents

Page 1 - CONDITIONER

P/NO : MFL67798033INSTALLATION MANUALOriginal instruction AIRCONDITIONERwww.lg.comPlease read this installation manual completely before installing th

Page 2 - IMPORTANT SAFETY INSTRUC

10ENGLISHFlaring work- Carry out flaring work using flaring tool as shown below.Firmly hold copper tube in a bar(or die) as indicated dimension in the

Page 3

11ENGLISH1 Always use the nitrogen.(not use oxygen, carbon dioxide, anda Chevron gas): Please use the following nitrogen pressure0.02MPa Oxygen – Pro

Page 4 - TABLE OF CONTENTS

12ENGLISHPIPE CONNECTIONS BETWEENINDOOR AND OUTDOOR UNITU4 Chassis (1FAN model)Connect the refrigerant pipe, and after the refrigerant leakage inspec-

Page 5 - INSTALLATION PROCESS

13ENGLISHTotal pipe length = A+B+C+D+a+b+c+d+e ≤ 150mLLongest pipe length Equivalent pipe length(*)A+B+C+D+e ≤ 80m A+B+C+D+e ≤ 100mlLongest pipe lengt

Page 6 - Air inlet grille

14ENGLISHWARNING• It is recommended that difference of piping length for pipesconnected to the Indoor Unit is minimized. Performance differ-ence betwe

Page 7 - 500 or less

15ENGLISHWARNING• Regulation for refrigerant leakage: the amount of refrigerant leakage should satisfy the followingequation for human safety.If the

Page 8 - Secure minimum intake area

16ENGLISH• When the number of indoor units to be connected to the branchpipes is less than the number of branch pipes available for connec-tion then c

Page 9 - - Remove before Installation

17ENGLISH[unit:mm]Leak testLeak test should be made by pressurizing nitrogen gas to 3.8MPa(38.7kgf/cm2). If the pressure does not drop for 24 hours, t

Page 10 - R=0.4~0.8

18ENGLISHNOTE!Always add an appropriate amount of refrigerant. (For the refrigerant addi-tional charge) Too much or too little refrigerant will cause

Page 11 - Nitrogen substitution method

19ENGLISHABEBIABDC1m1mDFGBGDBHIJAⒶ SleeveⒷ Heat insulating materialⒸ LaggingⒹ Caulking materialⒺ BandⒻ Waterproofing layerⒼ Sleeve with edgeⒽ Lagging

Page 12 - INDOOR AND OUTDOOR UNIT

2ENGLISH• Do not cool excessively indoors. This may be harmful for your healthand may consume more electricity.• Block sunlight with blinds or curta

Page 13 - Refrigerant piping system

20ENGLISHCAUTIONWhen the 400 volt power supply is applied to “N” phase by mistake,check damaged parts in control box and replace them.!Side panelWARNI

Page 14 - 500mm or more

21ENGLISH- Use a separate power supply for the Outdoor Unit and Indoor Unit.- Bear in mind ambient conditions (ambient temperature,direct sun-light, r

Page 15 - Gas pipe

22ENGLISH- About more information of IO Module, please refer to IO Modulemanual.CAUTIONBe sure to turn off outdoor unit power before installation.!++※

Page 16 - Y branch pipe

23ENGLISHExample) Group number setting 1stnumber indicate the group number2nd number point out indoor unit numberSODU.B SODU.A IDU.B IDU.A CEN.B CEN.A

Page 17 - Leak Test and Vacuum drying

24ENGLISHCAUTION• Request installer to set the function during installation. • If ODU RPM changes, cooling capacity may go down.!Master unit PCB DIP s

Page 18 - Vacuum Mode

25ENGLISHDisplay Title Cause of ErrorIndoor unit related error0 1 -Air temperature sensor of indoor unitAir temperature sensor of indoor unit is open

Page 19 - ELECTRICAL WIRING

26ENGLISHDisplay Title Cause of Error5 0 *Omitting connection of R, S, T power of Outdoor Unit Omitting connection of outdoor unit5 1 *Excessive capac

Page 20 - Side panel

27ENGLISHCalculate minimum room capacityCalculate room capacity by regarding a portion as one room or thesmaller room.- With partition and with openin

Page 21 - (Main Switch)

28ENGLISHCAUTION• Air conditioners should not be installed in areas wherecorrosive gases, such as acid or alkaline gas, are produced.• Do not install

Page 22 - Automatic Addressing

[Representative] LG Electronics European Shared Service Center B.V.Krijgsman 1, 1186 DM Amstelveen, The Netherlands[Manufacturer] LG Electronics Inc.

Page 23 - B(D) A(C)

3• Do not reconstruct to change the settings ofthe protection devices.- If the pressure switch, thermal switch, orother protection device is shorted a

Page 24

4ENGLISH• Install and insulate the drain hose to ensure that wateris drained away properly based on the installation man-ual.- A bad connection may c

Page 25 - Self-Diagnosis Function

5ENGLISHThe foundation must be level evenOutdoor unit foundation workAvoid short circuits and ensure sufficient space is allowed for serviceInstallatio

Page 26

6ENGLISHAir inlet grille700[Unit : mm]Turn the air outlet side toward thebuilding's wall, fence or windbreak screen.WARNINGFix the outdoor unit f

Page 27 - CAUTION FOR REFRIGERANT LEAK

7ENGLISHIn case of obstacles on the discharge side1. Stand alone installationa500 or lessmore1,000 ora2. Collective installation1,000 or more100 ormor

Page 28 - Product information

8ENGLISHSeasonal wind and cautions in winter• Sufficient measures are required in a snow area or severe cold areain winter so that product can be oper

Page 29

9ENGLISH• Fix the unit tightly with bolts as shown below so that unit will not falldown due to earthquake or gust.• Use the H-beam support as a base s