INSTALLATION
19
ENGLISH
DIP Switch Setting
Indoor Unit
Outdoor Unit
In case that the products meet specific conditions, “Auto addressing” function can start automat-
ically with the improved speed by turning the DIP switch #3 of the outdoor unit and resetting the
power.
* Specific conditions:
- All names of the indoor units are ARNU****4
- The serial number of Multi V super IV (outdoor units) is after October 2013,
CAUTION
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
!
Function Description Setting Off Setting On Default
SW1 Communication N/A (Default) - - Off
SW2 Cycle N/A (Default) - - Off
SW3 Group Control
Selection of Master
or Slave
Master Slave Off
SW4
Dry Contact
Mode
Selection of Dry
Contact Mode
Wired/Wireless remote
controller
Selection of Manual or
Auto operation Mode
Auto
Off
SW5 Installation
Fan continuous oper-
ation
Continuous operation
Removall
- Off
SW6 Heater linkage N/A - - Off
SW7
Ventilator link-
age
Selection of
Ventilator linkage
Linkage Removal
Working
Off
Vane selection
(Console)
Selection of up/down
side Vane
Up side + Down side
Vane
Up side Vane
Only
Region selection
Selection tropical
region
General model Tropical model
SW8 Etc. Spare - - Off
DIP switch 7 segment
Outdoor Unit PCB Outdoor Unit DIP Switch
1,MFL69485408,영영 2016. 11. 23. 영영 1:20 Page 19