Installation Manual 23
Installation
ENGLISH
ARNU363B8A4, ARNU423B8A4, ARNU483B8A4, ARNU763B8A4,
ARNU963B8A4
(Unit : CMM(cfm))
Setting Value
60 40.5(1430) - - - - - - - -
65 52.7(1861) 39.3(1388) - - - - - - -
70 63.7(2249) 47.1(1663) - - - - - - -
75 71.1(2511) 56.9(2009) 44.7(1578) - - - - - -
80 76.3(2694) 69.7(2461) 55.2(1949) - - - - - -
85 83.3(2941) 78.6(2775) 67.4(2380) 55.9(1974) 31.8(1123) - - - -
91 89.7(3167) 87.1(3076) 78.9(2786) 67.6(2387) 54.2(1914) - - - -
95 93.4(3298) 91.4(3227) 86.1(3040) 77.0(2719) 66.4(2345) 50.6(1787) 30.0(1059) - -
100 93.4(3298) 91.4(3227) 88.3(3118) 84.9(2998) 75.9(2680) 69.5(2454) 60.8(2147) 43.1(1522) -
105 93.2(3291) 91.3(3224) 88.3(3118) 84.9(2998) 81.1(2864) 77.4(2733) 72.0(2542) 68.0(2401) 52.0(1836)
6(0.23) 9(0.35) 12(0.47) 15(0.59) 18(0.71) 20(0.79) 22(0.86) 23(0.90) 25(0.98)
Static Pressure(mmAq (in.Aq))
Note:
1. The above table shows the correlation between the air rates and E.S.P.
2. The above table shows the available E.S.P. range.
3. If the E.S.P. of the installed indoor is less than the lowest value(as mention in the table), indoor components can be failed.