9.
Indoor
left-right
swing
Handset
control
Change
function
will
not
function
Faulty
swing
motor
Replace
Connector
plug
Replace
or
repair
Relay
on
PCB
Replace
relay
or
PCB
10.
Power
on
but
indoor
fan
Handset
control
Change
function
lost
Hi
or
Med
or
Low
Faulty
motor
Replace
speed
Connector
plug
Replace
or
repair
3
relays
on
PCB
Replace
relay
11.
Condenser
fan
short
Outdoor
sensor
See
control
functions
cycles
on
cooling
Unit
location
Check
for air
recirculation
12.
High
discharge
pressure
Indoor
sensor
faulty
Replace
cooling
cycle
Dirty
condenser
coil
Clean
Gas
overcharge
Reduce
charge
Air
recirculation
Move
unit
Faulty
motor
Replace
Cap
tube
blocked
Replace
16.
System
not
cooling
PCB
relay
Replace
or
change
PCB
Low
gas
charge
Add
gas
and
leak
test
17.
High
suction
/
low
Reversing
valve
sticking
Replace
discharge
pressure
18.
Outdoor
coil
icing
up
Ambient
temp
low
Wait
for
de
-
ice
initiation
Dirty
condenser
coil
Clean
Outdoor
de
-
ice
sensor
faulty
Replace
PCB
faulty
Replace
Low
gas
charge
(heating)
Add
gas
and
leak
test
19.
Indoor
coil
icing
up
Indoor
set
point
too
low
Adjust
temperature
Dirty
filter
Clean
filter
Faulty
indoor
sensor
Replace
PCB
faulty
Replace
Indoor
fan
not
working
Replace
Low
gas
charge
Replace
Add
gas
and
leak
test
Comments to this Manuals