ENGLISH
CEILING DUCT TYPE AIR CONDITIONERS
INSTALLATION INSTRUCTIONS
• Please read this instruction sheet completely before installing the product.
When the power cord is wanted to replace, replacement work shall be performed by authorized
personnel only.
Installation work must be performed in accordance with national wiring standards by authorized
personnel only.
P/No.: 3828A20021G
Air filters(Optional)
Remote Controller
Air intake vents
(Side)
(Rear)
Air intake vents
Air outlet vents
Piping
Drain hose
Connecting wire
Control cover
Air outlet vents
(Side)
(Rear)
Air outlet
vents
Air intake
vents
Connecting Wire
Drain Hose
Connection Pipe
Control Cover
(Side)
(Rear)
Air intake
vents
Air outlet vents
Piping
Drain hose
Control cover
Connecting wire
Indoor Unit
Outdoor Unit
ENGLISH
Page view 0
1 2 3 4 5 6 ... 19 20

Summary of Contents

Page 1 - INSTALLATION INSTRUCTIONS

ENGLISHCEILING DUCT TYPE AIR CONDITIONERSINSTALLATION INSTRUCTIONS• Please read this instruction sheet completely before installing the product.• When

Page 2 - OUT-LINE OF INSTALLATION

10Flared connection (Union)Flared connection(Service valve, Ball valve)Use a seemliness tubeFactory chargedIndoorOutdoorREFRIGERANT PIPINGINSTALLATION

Page 3

ENGLISHOutdoorIndoorControl terminal boardControl boxControl box cover(On which the ElectricWiring Connection is put)Main terminal boardCover controlC

Page 4 - 2) Outdoor unit

123-1. Preparation of Piping3. Connecting Pipes to the Indoor UnitMain cause of gas leakage is defect inflaring work. Carry out correct flaring workin

Page 5 - 2. Indoor unit installation

ENGLISH6) Pipe bendingAnnealed copper pipe with small diameter (ø6.35 or ø9.52) can be easily bent manually. Inthis case, secure large R(radius) for t

Page 6

1) Connecting the pipes to theOutdoor unit1. Align the center of the pipings andsufficiently tighten the flare nut withfingers.2. Finally, tighten the

Page 7 - UNIT AND DRAIN PIPING

ENGLISH1) Connecting cables to the Indoor Unit Connect the wires to the terminals on the control board individually according to theoutdoor unit con

Page 8 - INSULATION, OTHERS

3) Connecting the cable to theOutdoor Unit1. Remove the Cover control from the unitby loosening a screw.Connect the wires to the terminals onthe contr

Page 9 - The lower part

ENGLISH4) Form the pipings 1. Wrap the connecting portion of indoorunit with the Insulation material andsecure it with two Plastic Bands. (for therigh

Page 10 - INSTALLATION OF OUT DOOR UNIT

7. Air Purging of the Connecting Pipes and the Indoor Unit18Indoor unitOutdoor unitLiquid sideCLOSEOPENVaccum pumpGas sideClosedClosed2-way valve/3-wa

Page 11 - OUTDOOR UNIT

8. Group Control9. Two Thermistor system10. High-Static Motor Connection (For 60K/48K Model)19ENGLISHIt operates maximum 16 Units by only one Wired Re

Page 12 - 3-1. Preparation of Piping

1.The following should be always observed for safety ...32. Installation of Indoor, Outdoor unit3. Connecting Pipes to the

Page 13 - 6) Pipe bending

11. External Static Pressure & Air Flow20Static Pressure(mm Aq) 0 2 4 6 8 10 15Model Name Step CMM CMM CMM CMM CMM CMM CMMHigh 25.5 23.5 21.5 18.5

Page 14 - Outdoor unit

ENGLISH31. The following should be always observed for safety• Please report to or take consent by the supply authority before connecting to the syste

Page 15 - 2) Clamping of cables

4Indoor unitOutdoor unitBAMore than30cmMore than30cmMore than70cmSunroofFence orobstaclesH600600Top view(unit: mm)Front viewFrontInspection hole(600X6

Page 16 - Outdoor Unit

ENGLISH2. Indoor unit installation Installation of UnitInstall the unit above the ceiling correctly.• Apply a joint-canvas between the unit andduct t

Page 17 - 4) Form the pipings

6• Select and mark the position for fixingbolts.• Drill the hole for set anchor on the faceof ceiling.• Insert the set anchor and washer ontothe suspe

Page 18 - Indoor unit

ENGLISHCeilingCAUTION1~3mmDrainage holeDrainage holeU-TrapBCA ≥ 70mmB ≥ 2CC ≥ 2 x SPSP = External Pressure(mmAq)Ex) External Pressure= 10mmAqA ≥ 70mmB

Page 19 - 9. Two Thermistor system

8• Drill the piping hole with 70mm dia, holecore drill.• Piping hole should be slightly slant to theoutdoor side.INSULATION, OTHERSInsulate the joint

Page 20

ENGLISH9INSTALLATION OF REMOTE CONTROL BOXInstall the remote control boxand cord correctly.• Although the room temperature sensor is in the indoor uni