INSTALLATION MANUALAIR CONDITIONER • Please read this installation manual completely before installing the product.• Installation work must be perfor
10 Indoor UnitInstallationPreparation of Piping1. Cut the pipes and the cable. Use the accessory piping kit or the pipes purchasedlocally. Measure t
Installation Manual 11ENGLISHInstallation1. Remove the cap and turn the valve counter clockwise with the hexagon wrench.2. Turn it until the shaft st
12 Indoor Unit1. Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C).2. Precautions in hig
Installation Manual 13ENGLISHInstallationConnect the wires to the terminals on the control board individually according to the outdoor unit connectio
14 Indoor UnitInstallationCAUTION: After the confirmation of the above conditions, prepare the wiring as follows:1) Never fail to have an individual p
Installation Manual 15ENGLISHInstallationWIERED REMOTE CONTROLLER INSTALLATION• Since the room temperature sensor is in the remote controller, the re
16 Indoor UnitInstallation of Wired Remote Controller22133<Wire guide grooves>1. Please fix tightly using provided screw after placing remote co
Installation Manual 17ENGLISH4. Please connect indoor unit and remote controller using connection cable.5. Please use extension cable if the distance
18 Indoor Unit14571110982361312Please attach the inform label inside of the door.Please choose proper language depend on your country.1415Name and fun
Installation Manual 19ENGLISHDip Switch SettingFor Multi V Models, Dip switch 1, 2, 6, 8 must be set OFF.Function Description Setting Off Setting On
2 Indoor UnitIMPORTANT!CAUTION: Improper installation, adjustment, alteration, service or maintenance can void the warranty.The weight of the condensi
20 Indoor UnitGroup Control SettingWired remote controller 1 + Standard Indoor Units Dip Switch in PCB (Cassette and Duct Type indoor units)1. It is p
Installation Manual 21ENGLISH2. Group Control 2Wired remote controllers + Standard Indoor UnitsIt is possible to control N indoor units by wired remo
22 Indoor UnitMixture connection with indoor units and Fresh Air Intake UnitIn case of connecting with standard indoor unit and Fresh Intake Unit, sep
Installation Manual 23ENGLISHWired remote controller 2 + Indoor unit 11. It is possible to connect two wired remote controllers with one indoor unit.
24 Indoor UnitSlaveMas te rMasterPZCWRCG3Master S lavePZCWRC2Indoor unit 2 EA +Wired remote controller❈ PZCWRCG3 cable used for connection ❈ PZCWRC2 c
US1. Please call the installing contractor of your product, as warranty service will be provided by them.2. If you have service issues that have not b
Installation Manual 3ENGLISHFloor Standing Concealed Floor Standing Type Indoor Unit Installation ManualTABLE OF CONTENTS❏ Four type "A" s
4 Indoor UnitSafety PrecautionsSafety PrecautionsTo prevent injury to the user or other people and property damage, the following instructions must be
Installation Manual 5ENGLISHSafety Precautions OperationDo not modify or extend thepower cable.• There is risk of fire or electric shock.Do not let
6 Indoor UnitSafety PrecautionsAlways check for gas (refriger-ant) leakage after installation orrepair of product.• Low refrigerant levels may causefa
Installation Manual 7ENGLISHIntroductionIntroductionWired Remote Controller Air OutletControl panelControl panelAir FilterAir InletAir InletAir filte
8 Indoor UnitInstallationInstallationIndoor unitInstall the air conditioner in the location that satisfies the fol-lowing conditions.• The place shall
Installation Manual 9ENGLISHInstallationBolt pitchUnit:mm(inch)CEA, CEU 858(33-3/4)CFA, CFU 1136(44-3/4)TypeA(1)(1)(2)(2)(3)198(7-13/16)A270(7-5/8)[U