INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national
wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading
it thoroughly.your set and retain it for future reference.
P/NO : MFL63748901
www.lg.com
MODELS: ARWN Series
ENGLISH FRANCAIS
ESPAÑOL
Page view 0
1 2 3 4 5 6 ... 78 79

Summary of Contents

Page 1 - AIR CONDITIONER

INSTALLATION MANUALAIR CONDITIONER • Please read this installation manual completely before installing the product.• Installation work must be perform

Page 2 - TABLE OF CONTENTS

Environment-friendly Alternative Refrigerant R410A 10 Outside UnitSelect the Best LocationSelect space for installing outside unit, which will meet th

Page 3 - Safety Precautions

Installation space Installation Manual 11ENGLISHInstallation space Individual InstallationCollective / Continuous InstallationRequired the minimum sp

Page 4

12 Outside UnitTwo Layer InstallationSpace required for two layer installation as shown below considering passage for air and people.: Service areaH-B

Page 5

Installation Manual 13ENGLISHInstallation space Water control Water control • Keep the water temperature between 10~45°C(50~113°F). Other it may caus

Page 6 - 6 Outside Unit

14 Outside UnitStandard table for water purity controlThe water may contain many foreign substances and hence may influence the performance and lifeti

Page 7 - Installation Process

Installation Manual 15ENGLISHLifting methodLifting method• When carrying the suspended, unit pass the ropes under the unit and use the two suspension

Page 8 - Outside units Information

16 Outside UnitInstallationLocation of anchor boltThe location of anchor bolt59(2-5/16)50(2)13(1/2)599(23-19/32)658(25-29/32)[Unit: mm(inch)]Installat

Page 9 - ■ Heat Pump

Installation Manual 17ENGLISHInstallationPreparation of Piping1) Cut the pipes and the cable. Use the accessory piping kit or the pipes purchasedloc

Page 10 - Select the Best Location

18 Outside UnitInstallation1. Remove the cap and turn the valve counter clockwise with the hexagon wrench.2. Turn it until the shaft stops.Do not appl

Page 11 - Installation space

Installation Manual 19ENGLISHInstallation1. Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over1

Page 12 - Two Layer Installation

2 Outside UnitARWN Series Outside unit Installation ManualTABLE OF CONTENTSSafety Precautions ...

Page 13 - Water control

20 Outside UnitRefrigerant piping installationWARNINGAfter completing work, securely tighten both service ports and caps so that gas does not leak. Re

Page 14 - [Reference]

Installation Manual 21ENGLISHRefrigerant piping installationSlaveOutside Unit MasterOutside Unit Slave1OutsideUnit Slave2OutsideUnit MainOutside Unit

Page 15 - Sub line

22 Outside UnitRefrigerant piping installation3 Outside UnitsY branchA B To outside unitTo branch piping or indoor unitABFacingupwardsFacingdownwardsW

Page 16 - Installation

Installation Manual 23ENGLISHRefrigerant piping installation1) Water pipe system diagram• The water pressure resistance of the water pipe system of t

Page 17 - Preparation of Piping

24 Outside UnitWater pipeconnectionWater pipe inlet Water pipe outlet mm inch (kN) (kgf) (kN) (kgf) (N.m) (kgf.m)(N.m) (kgf.m) 12.7 1/2 3.5 350 2.

Page 18 - R=0.4~0.8

Installation Manual 25ENGLISHProduct protection deviceDevice protection unitStrainer on water pipeTo protect the water cooling type product, you must

Page 19 - HEAT INSULATION

Installation of flow switch• The flow switch must be installed at the horizontal pipe of the heat water supply outlet of the product and check the dir

Page 20 - Ball Valve(Liquid Pipe)

Installation Manual 27ENGLISHRefrigerant piping system Refrigerant piping system Y branch method➲ Refrigerant pipe diameter frombranch to branch (B,C

Page 21 - Connection of Outside units

28 Outside UnitBelow 2m(6.6ft)MasterSlaveIndoor unitdirectionBelow 10mL Below 150m(492ft)Below H 50m(164ft)l Below 40m(131ft)Below 15m(49ft)➲Slave out

Page 22 - 3 Outside Units

Installation Manual 29ENGLISHRefrigerant piping system 10m orlessL150m(492ft)l 40m(131ft)Slave2Slave1MasterBelow 2m(6.6ft)(h1)Indoor unitdirectionH 5

Page 23 - Installation of water pipe

Installation Manual 3ENGLISHSafety PrecautionsSafety PrecautionsTo prevent injury to the user or other people and property damage, the following inst

Page 24 - Water pipe outlet

30 Outside UnitHeader branch methodL Below 150m(492ft)Below H 50m(164ft)l Below 40m(131ft)Below 15m(49ft)➲Total refrigerant pipe length = A +a +b +c +

Page 25 - Device protection unit

Installation Manual 31ENGLISHRefrigerant piping system MasterSlaveL Below 150m(492ft)H Below 50m(164ft)l Below 40m(131ft)Below 15m(49ft)Below 10mBelo

Page 26 - Flow switch work

32 Outside UnitBranch pipe can not be used after header3. When installing 3 outside unitsEx)6 Indoor Units connectedⒶ : Outside UnitsⒷ : Header branch

Page 27 - Refrigerant piping system

Installation Manual 33ENGLISHRefrigerant piping system Y/Header branch method➲ Outside unit Ⓐ~ 1st Y branchpart Ⓑ : Main pipe diameter (A) L Below 15

Page 28 - Ex) 5 indoor units connected

34 Outside UnitMasterSlaveL Below 150m(492ft)H Below 50m(164ft)h Below 15m(49ft)Below 10mBelow 2m(6.6ft)l Below 40m(131ft)➲Slave outside unit ~ Conn

Page 29 - Outside unit capacity

Installation Manual 35ENGLISHRefrigerant piping system Branch pipe can not be used after header3. When installing 3 outside unitsEx) 5 Indoor Units c

Page 30 - Below 15m(49ft)

36 Outside Unit‘ Indoor unit connecting pipe from branch (a~f)‘ Equivalent piping length for Y Branch and other pipes can be calculated with following

Page 31 - Ex) 6 indoor units connected

Installation Manual 37ENGLISHRefrigerant piping system Oil trap application method between outside units• Because of the possibility of oil being acc

Page 32 - 6 Indoor Units connected

38 Outside UnitCalculation of amount of refrigerantRefrigerant piping system The calculation of the additional charge should take into account the len

Page 33 - Y/Header branch method

Installation Manual 39ENGLISHRefrigerant piping system ▶ Regulation for refrigerant leakage: the amount of refrigerant leakage should satisfy the fo

Page 34 - 34 Outside Unit

4 Outside UnitSafety PrecautionsVentilate before operating air conditioner when gasleaked out.• It may cause explosion, fire, and burn.Securely instal

Page 35 - Ex) 5 Indoor Units connected

40 Outside UnitRefrigerant piping system To Outside UnitSealed PipingAABAB1. Use the following materials for refrigerant piping.• Material: Seamless p

Page 36 - Indoor unit connection

Installation Manual 41ENGLISHRefrigerant piping system Branch pipe FittingY branchA B To Outside UnitTo Branch Piping or Indoor UnitABFacingupwardsFa

Page 37

42 Outside UnitRefrigerant piping system • When the number of indoor units to be connected to the branch pipes is less than the number of branchpipes

Page 38 - Total amount(kg)

Installation Manual 43ENGLISHRefrigerant piping system Thermal insulation of refrigerant pipingHeatinsulationmaterialOutercoveringAdhesive + Heat - r

Page 39 - Installation Manual 39

44 Outside UnitY branch pipe and header branch pipe type Y branch pipeY branch pipe and header branch pipe type Models Gas pipe Liquid pipe[unit:mm(in

Page 40 - 40 Outside Unit

Installation Manual 45ENGLISHY branch pipe and header branch pipe type Header[unit:mm(inch)]Models Gas pipe Liquid pipe4 branchARBL0547 branchARBL057

Page 41 - Branch pipe Fitting

46 Outside UnitLeakage test and vacuum Leak testCloseIndoor unitNitrogen gasOutside unitClose CloseCloseLiquide pipeLiquide pipeLiquide pipeGas pipeGa

Page 42 - Insulate the header using

Installation Manual 47ENGLISHLeakage test and vacuum VacuumVacuum drying should be made from the service port provided on the outside unit’s service

Page 43 - Penetrations

48 Outside UnitElectrical WiringElectrical WiringRemotecontrolRemotecontrolRemotecontrolRemotecontrolIndoorUnitOutside Unit Outside UnitOutside UnitIn

Page 44 - Y branch pipe

Installation Manual 49ENGLISHElectrical WiringMaster Slave1 Slave2Master Slave1 Slave2Master Slave1 Slave2Master Slave1 Slave2RemotecontrollerRemotec

Page 45 - [unit:mm(inch)]

Installation Manual 5ENGLISHSafety PrecautionsDo not install the product where it is exposed to sea wind (salt spray) directly.• It may cause corrosi

Page 46 - Leakage test and vacuum

50 Outside UnitElectrical Wiring- Unscrew all the screw, pull out the panel.- Connect the transmission wire between outside unit and indoor unit,the c

Page 47 - 2Units, 3Units

Installation Manual 51ENGLISHElectrical WiringTransmission and Power Lines1) Transmission cable• Types : shielding wire• Diameter : over 1.25mm2• Max

Page 48 - Electrical Wiring

52 Outside UnitElectrical Wiring1. Use a separate power supply for the Outside Unit and Indoor Unit.2. Bear in mind ambient conditions (ambient temper

Page 49 - Power wire

Installation Manual 53ENGLISHElectrical Wiring1. 60Hz34 34 34The GND terminal is a '–' terminal for the central controller, not Ground Lin

Page 50 - Front Panel

54 Outside UnitElectrical WiringPower supply switch(Switch fuse : ELCB)Power supply switch(Switch)Power supply switch(Switch)3 Phase 3 Wires Power lin

Page 51 - Transmission and Power Lines

Installation Manual 55ENGLISHElectrical WiringPower supply switch(Switch fuse : ELCB)3 Phase 3 Wires Power line(L1, L2, L3)Transmission line (3 line)

Page 52

56 Outside UnitElectrical Wiring◆ Example Connection of Communication Cable[BUS type]• Connection of communication cable must be installed like below

Page 53 - Pull Box(Installer option)

Installation Manual 57ENGLISHElectrical WiringConnection method of the connecting cable (Example)1. Make a hole appropriate for the passage of connec

Page 54 - 2 Outside Units

58 Outside UnitElectrical WiringDip switch setting1. Location of setting switch 2. Dip switch setting1) Set the dip switch and turn on the power of th

Page 55 - Installation Manual 55

Installation Manual 59ENGLISHElectrical Wiring Master Outside SettingSW01B Setting SW02B Setting RemarkNormal mode at shippingfactory1234567ON123456

Page 56 - [STAR type]

6 Outside UnitSafety PrecautionsWhen wiring:Electrical shock can cause severe personal injury or death. Only a qualified,experienced electrician shoul

Page 57 - Conduit

60 Outside UnitElectrical WiringFunction SW01B Setting SW02B Setting RemarkStandard mode at shippingfactorylongest PipeLengthForced Oil Return1234567O

Page 58 - Dip switch setting

Installation Manual 61ENGLISHElectrical Wiring• The address of indoor units would be set by auto addressing1) Wait for 3 minutes after applying power

Page 59 - ■ Master Outside Setting

62 Outside UnitElectrical WiringGroup Number settingGroup Number setting for Indoor Units① Confirm the power of whole system(Indoor Unit, Outside Unit

Page 60 - 60 Outside Unit

Installation Manual 63ENGLISHElectrical WiringCool and Heat Selector Installation and Connection • Connect wires as below figure at the hole of backs

Page 61 - Indoor unit auto addressing

64 Outside UnitTest RunTest RunWater supply system test run• Before executing the test run for the product, you must first test the heat source water

Page 62 - Group Number setting

Installation Manual 65ENGLISHHow to Cope with Abnormal Test RunItemPhenomenonCause Checkpoint and resolutionCheck whether the heat source water suppl

Page 63 - : Developing

66 Outside UnitTest RunMaintenance of plate type heat exchanger❈ When CH24 or CH180 error occurs during the test operation of the heater, the inside o

Page 64 - Test Run

Installation Manual 67ENGLISHDaily check/managementMaintenance/Repair checklistTest Run1. Water quality controlThe plate type heat exchanger is not s

Page 65 - Precaution before test run

68 Outside UnitTest RunSelf-Diagnosis FunctionError Indicator• This function indicates types of failure in self-diagnosis and occurrence of failure fo

Page 66 - 66 Outside Unit

Installation Manual 69ENGLISHTest RunDisplay Error item Root cause of errornumberInitial operation failure due to slave1 outside unit Variable speed

Page 67 - : Check mark)

Installation ProcessInstallation Manual 7ENGLISHInstallation ProcessThe foundation must be level evenOutside unit foundation workAvoid short circuits

Page 68 - Self-Diagnosis Function

70 Outside UnitTest RunDisplay Error item Root cause of errornumberSlave1 outside unit Variable speed compressor current detection (CT)sensor disconne

Page 69 - Installation Manual 69

Installation Manual 71ENGLISHTest RunDisplay Error item Root cause of errornumberWhen the inverter controller signal is not received from the master

Page 70 - 70 Outside Unit

72 Outside UnitTest Run Refer to the troubleshooting guide of service technical manual for each error. Display Error item Root cause of errornumberMa

Page 71 - Installation Manual 71

Installation Manual 73ENGLISHCooling tower applied method Cooling tower applied method [Open type cooling tower + Second heat exchanger] Heat exchang

Page 72 - 72 Outside Unit

74 Outside UnitCaution For Refrigerant LeakThe installer and system specialist shall secure safety against leakage according to local regulations or s

Page 73 - Cooling tower applied method

Installation Manual 75ENGLISHCaution For Refrigerant Leak(3) With partition and without opening which serve as passage of air to adjoining roomCalcul

Page 74 - Caution For Refrigerant Leak

76 Outside UnitWater Solenoid Valve ControlCN_26CN_24CN_22INTERNETMAIN PCBC_Box DDC BMSFlow SwitchSolenoid ValveWater OutWater InCN_26CN_24CN_22MAIN P

Page 75

Variable Water Flow Control KIT(Accessory)Installation Manual 77ENGLISHVariable Water Flow Control KIT(Accessory)1. Shut off the main power line of o

Page 77 - Installation Manual 77

USA, press #2 for PTAC, TTWUSA, press #3 for DFS, Multi VCANADA 888-865-3026888-865-30261-888-LG-Canadawww.lge.comLG Customer Information CenterRegi

Page 78 - 78 Outside Unit

Outside units Information8 Outside UnitOutside units InformationPower Supply: Outside Unit (3Ø, 208/230V, 60Hz) Heat pump• Ratio of the running Indoo

Page 79 - 1-888-LG-Canada

Outside units InformationInstallation Manual 9ENGLISHPower Supply: Outside Unit (3Ø, 460V, 60Hz) Heat Pump System Capacity