LM50 2004-E1MPS Variable Multi Split SYSTEMFree Joint, 50Hz, R410A
2004 Product Data 9Features & BenefitEnvironment Friendly Refrigerant :- LG Air conditioners uses environment friendly refrigerant. Which don&a
10 MPS Variable Multi Split System(50Hz, R410A)
2004 Product Data 11Part 2MPS Variable Multi-Split SystemR410A, Cooling Only/Heat PumpAMNC076LQL0 AMNC096AP*1AMNC096LQL0 AMNC126AP*1AMNC126
12 MPS Variable Multi Split System(50Hz, R410A)1. Power SupplyType Outdoor Unit Power SupplyCooling Only1Ø, 220~240V, 50HzHeat PumpNote : Power Supply
2004 Product Data 132. Model Number Nomenclature2.1 Indoor Units2.2 Outdoor UnitsAMN H 607QL L 0Chassis NameSerial NumberCombination of FunctionsAR
14 MPS Variable Multi Split System(50Hz, R410A)3. Outline of SystemThe system has number of indoor units attached to an outdoor unit which saves energ
2004 Product Data 153. Outline of System3.3 External Appearance of Indoor UnitsWall MountedAMNC076LQL0 AMNH076LQL0 AMNC096LQL0 AMNH096LQL0AMNC126
16 MPS Variable Multi Split System(50Hz, R410A)4. List of FunctionsModelFeaturesAirflow Direction Control(Left & Right) Manual Manual Manual Manua
2004 Product Data 175. Specifications1764(2051) 2267(2638) 3024(3515 4536(5275) 5795(67407000 9000 12000 18000 23000 ----------5.5(194) 6.0.(212) 9
18 MPS Variable Multi Split System(50Hz, R410A)5. SpecificationsHeat PumpNominal Cooling Capacity ★ kcal/hr(W)Btu/hrNominal Heating Capacity ★ kcal/hr
2004 Product Data 1General DescriptionThank you very much for your special patronage of LG air-conditioners.A high-grade, high-quality, advanced in
2004 Product Data 195. SpecificationsNotes: 1. Capacities are based on the following conditions:Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C
20 MPS Variable Multi Split System(50Hz, R410A)5. SpecificationsNotes: 1. Capacities are based on the following conditions:Cooling: - Indoor Temperatu
2004 Product Data 216. Combination TableCooling6.1 Cooling Only6.1.1 A2UC146FA0Combination(k Btu)Capacity (Btu/h)CoolingInput(W)Current(A)EER(Btu/h
Cooling6.1.4 A4UC306FA022 MPS Variable Multi Split System(50Hz, R410A)6. Combination TableCombination(k Btu)Capacity (Btu/h)CoolingUnit-A Unit-B Unit-
2004 Product Data 236. Combination TableCoolingHeatingHeating6.2 Heat Pump6.2.1 A2UH146FA0Combination(k Btu)Capacity (Btu/h)CoolingUnit-A Unit-B Un
24 MPS Variable Multi Split System(50Hz, R410A)6. Combination TableCooling6.2.3 A3UH216FA0 HeatingCombination(k Btu)Capacity (Btu/h)CoolingUnit-A Unit
2004 Product Data 256. Combination TableCooling6.2.4 A4UH306FA0 Combination(k Btu)Capacity (Btu/h)CoolingUnit-A Unit-B Unit-C Unit-D TotalInput(W)C
26 MPS Variable Multi Split System(50Hz, R410A)6. Combination TableHeatingCombination(k Btu)Capacity (Btu/h)HeatingUnit-A Unit-B Unit-C Unit-D TotalIn
2004 Product Data 277. Dimensional DrawingsAMNC-LQ/LR/LT, AMNH-LQ/LR/LTW8249001090H260285314D155156172ModelAMNC/H076LQL0AMNC/H096LQL0AMNC/H126LRL0A
28 MPS Variable Multi Split System(50Hz, R410A)W570H568D129ModelAMNC/H096AP*1AMNC/H126AP*1(unit : mm)7. Dimensional DrawingsØ 9.52Ø 6.359, 12kGasLiqui
2 MPS Variable Multi Split System(50Hz, R410A)
2004 Product Data 297. Dimensional DrawingsA2UC146FA0, A2UH146FA07.2 Outdoor UnitsWL6L7 L8 L9L4HDL1L2L3L5L10Gas side3-way valveLiquid side2-way val
30 MPS Variable Multi Split System(50Hz, R410A)7. Dimensional DrawingsA2UC186FA0, A2UH186FA0WDL1L2L9L4L3HL10L10L10L8Gas side3-Way valveLiquid side2-Wa
2004 Product Data 317. Dimensional DrawingsA3UC216FA0, A3UH216FA0WL5L6 L7 L8L3HDL1L2L4L10L9Gas side3-way valveLiquid side2-way valveL10L10L10L10W m
32 MPS Variable Multi Split System(50Hz, R410A)7. Dimensional DrawingsA4UC306FA0, A4UH306FA076.54-holes for anchor bolts50505050505032064160160 550106
2004 Product Data 338. Wiring Diagrams3854A20135WCN-TH1THERMISTOR(OUT-PIPE)THERMISTOR(IN-PIPE)THERMISTOR(ROOM)CN-TH2CN-U/DCN-MOTORCN-POWERAC PCB AS
34 MPS Variable Multi Split System(50Hz, R410A)8. Wiring DiagramsART COOL TypeCONNECT PCB ASMDISPLAYPCB ASMAC PWB ASM DC PWB ASMCN-UD(BL)CN-LR1(WH)CN-
2004 Product Data 358. Wiring DiagramsA2UC146FA08.2 Outdoor UnitNotes: BL BLUE BK BLACK BR BROWNRD RED OR ORANGE WH WHITEYL YELLOW GN/YL GREEN/YELL
36 MPS Variable Multi Split System(50Hz, R410A)8. Wiring DiagramsA2UC186FA0OUTDOOR WIRING DIAGRAMTMTB1OLPOLPBLBLBLBRBRBRBLORYL1(L)2(N)33MAIN PWB ASSYC
2004 Product Data 378. Wiring DiagramsA3UC216FA0OUTDOOR WIRING DIAGRAMTB1BLBLBLBRBRORYLRDBRBLMAIN PWB ASSYP/NO : 3854A20392BTMGN/YL1(L)2(N)3332(N)2
38 MPS Variable Multi Split System(50Hz, R410A)8. Wiring DiagramsA4UC306FA0OUTDOOR WIRING DIAGRAMTM32(N)1(L)332(N)2(N)1(L)1(L)3TB1BLBLBLBRBRORYLRDWHBR
2004 Product Data 3LG Airconditioners Product DataTABLE OF CONTENTSTable of contents PagePart 1 Features...
2004 Product Data 398. Wiring DiagramsA2UH146FA0OUTDOOR WIRING DIAGRAMMAINPOWERAS/VCMFMoP/NO : 3854A20375ABS/VB/PS/V4WVMAIN PCB ASSYBKBKBKBRBKBKT/B
40 MPS Variable Multi Split System(50Hz, R410A)8. Wiring DiagramsA2UH186FA0OUTDOOR WIRING DIAGRAMTB1TB2OLPOLPBRBLBLBL BRBL BRORYLMAIN PWB ASSYCN-COM(W
2004 Product Data 418. Wiring DiagramsA3UH216FA0OUTDOOR WIRING DIAGRAMBLMAIN PWB ASSY4WVP/NO : 3854A20216UCN-LEV2(BL)CN-LEV3(YL)LEVBLEVCLEVACN-LEV1
42 MPS Variable Multi Split System(50Hz, R410A)8. Wiring DiagramsA4UH306FA0OUTDOOR WIRING DIAGRAMCN-COM(WH)CN-POWER(WH)CN-TH1FUSET3.15APIPE TEMPSENSOR
2004 Product Data 439. Piping DiagramsHeat ExchangerC.F.Flndoor unit:Cooling: ThermistorGasØ9.52(3/8)Ø12.7(1/2)LiquidØ6.35(1/4)ModelAMNC076LQL0AMNC
44 MPS Variable Multi Split System(50Hz, R410A)9. Piping DiagramsHeat ExchangerC.F.Flndoor unit:Cooling: Thermistor:Heating[unit:mm(inch)]Refrigerant
2004 Product Data 459. Piping DiagramsRoom BAccumulatorCompressorHeatExchangerHeaderRoom ARoom BRoom AOUTDOOR UNITField PipingGasField PipingLiquid
46 MPS Variable Multi Split System(50Hz, R410A)9. Piping DiagramsLEV-ALEV-BLEV-CHeaderRoom CRoom AField PipingLiquidRoom BRoom CRoom AField PipingGasR
2004 Product Data 479. Piping DiagramsRoom BAccumulatorCompressorHeatExchangerHeaderRoom AOUTDOOR UNITField PipingGasReversingValveRefrigerant Flow
48 MPS Variable Multi Split System(50Hz, R410A)9. Piping DiagramsAccumulatorLowPressureHeatExchangerCheckValve(2)CheckValve(1)ReversingValveOUTDOOR UN
4 MPS Variable Multi Split System(50Hz, R410A)
2004 Product Data 4910. Capacity Table10.1 A2UC146FA0[Cooling Capacity]10.2 A2UC186FA0[Cooling Capacity]TC PI TC PI TC PI TC PI TC PI TC PIkW kW kW
50 MPS Variable Multi Split System(50Hz, R410A)10. Capacity Table10.3 A3UC216FA0[Cooling Capacity]TC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW
2004 Product Data 5110. Capacity Table10.4 A4UC306FA0[Cooling Capacity]TC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombin
52 MPS Variable Multi Split System(50Hz, R410A)10. Capacity TableTC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombinationCapa
2004 Product Data 5310. Capacity TableTC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombinationCapacity Index(kBtu/h)Outdoo
54 MPS Variable Multi Split System(50Hz, R410A)10. Capacity Table10.5 A2UH146FA0[Cooling Capacity][Heating Capacity]TC PI TC PI TC PI TC PI TC PI TC P
2004 Product Data 5510. Capacity Table10.6 A2UH186FA0[Cooling Capacity]Heat PumpTC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW
56 MPS Variable Multi Split System(50Hz, R410A)10. Capacity Table[Heating Capacity]TC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW
2004 Product Data 5710. Capacity TableHeat Pump10.7 A3UH216FA0[Cooling Capacity]TC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW
58 MPS Variable Multi Split System(50Hz, R410A)10. Capacity Table[Heating Capacity]TC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW
2004 Product Data 5Part 1Features
2004 Product Data 5910. Capacity Table10.8 A4UH306FA0[Cooling Capacity]TC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombin
60 MPS Variable Multi Split System(50Hz, R410A)10. Capacity TableTC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombinationCapa
2004 Product Data 6110. Capacity TableTC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombinationCapacity Index(kBtu/h)Outdoo
62 MPS Variable Multi Split System(50Hz, R410A)10. Capacity TableTC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombinationCapa
2004 Product Data 6310. Capacity TableHeat PumpTC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombinationCapacity Index(kBtu
64 MPS Variable Multi Split System(50Hz, R410A)11. Operation LimitsItem RangeInlet air temperature(Cooling)Inlet air temperature(Heating)Power source
2004 Product Data 6512. Air Velocity and Temperature Distributions(Reference Data)7k Btu/h Model12.2 ART COOL Type12k Btu/h ModelAir velocity [m/s]
66 MPS Variable Multi Split System(50Hz, R410A)13. Sound LevelsOverallSound Pressure LevelAMNC/H076LQL0 AMNC/H096LQL0 AMNC/H126LRL0 AMNC/H186LTL0 AMNC
2004 Product Data 67ART COOL13. Sound LevelsOverallSound Pressure LevelAMNC/H096AP*1 AMNC/H126AP*1Notes:- Sound measured at 1m away from the cen
68 MPS Variable Multi Split System(50Hz, R410A)13. Sound Levels13.2 Outdoor UnitOverallSound Pressure LevelA2UC/H146FA0 A2UC/H186FA0 A3UC/H216FA0A4UC/
6 MPS Variable Multi Split System(50Hz, R410A)Features & BenefitMPS(Multi Power System) Variable Control : (Except A2UC146FA0,A2UH146FA0)Big Energ
2004 Product Data 6914. Installation14.1 Piping Length & Refrigerant ChargeThe maximun allowable level and piping length7.5mIt does not matter
70 MPS Variable Multi Split System(50Hz, R410A)14. Installation• There should not be any heat source or steam nearthe unit.• There should not be any o
2004 Product Data 7114. Installation14.2.2 Outdoor Unit• If an awning or canopy is built over the unit to prevent direct sunlight or rain exposure,
72 MPS Variable Multi Split System(50Hz, R410A)14. Installation14.4 Connecting Pipings and the cable to Outdoor unit14.4.1 Connecting the pipings to t
2004 Product Data 7314. InstallationConnecting the cable to the Outdoor unit.CAUTION: Provide a circuit breakerbetween power source and the unit as
74 MPS Variable Multi Split System(50Hz, R410A)14. InstallationCAUTIONAfter the confirmation of the above conditions, prepare the wiring as follows.1.
2004 Product Data 7514. Installation14.5 Drain Pipe Work❑ Drain pipe gradient and support 1) - The drain pipe must be fitted at a gradient of at le
76 MPS Variable Multi Split System(50Hz, R410A)15. Function of Remote ControllerONOFFCANCELAUTO CLEANSET135491017181672813141511612Cooling OperationAu
P/No.: 3828A20428F 20 Yoido-dong, Youngdungpo-gu, Yoido P.O.Box 355Seoul 150-721, KoreaPhone: 3777-7969 Fax: 3777-5137/8http://www.lge.comhttp://biz.
2004 Product Data 7Features & Benefit90(Min)0100200300400500(ppm)6030Nano Filter++++++++++++++++Normal FilterAir Purifying System- It not only
8 MPS Variable Multi Split System(50Hz, R410A)Features & BenefitVertical TemperatureDifferenceHorizontal TemperatureDifferenceImproved value of th