LM50 2004-E1
MPS Variable Multi Split SYSTEM
Free Joint, 50Hz, R410A
Page view 0
1 2 3 4 5 6 ... 77 78

Summary of Contents

Page 1 - LM50 2004-E1

LM50 2004-E1MPS Variable Multi Split SYSTEMFree Joint, 50Hz, R410A

Page 2 - LG Electronics Inc

2004 Product Data 9Features & BenefitEnvironment Friendly Refrigerant :- LG Air conditioners uses environment friendly refrigerant. Which don&a

Page 3

10 MPS Variable Multi Split System(50Hz, R410A)

Page 4 - TABLE OF CONTENTS

2004 Product Data 11Part 2MPS Variable Multi-Split SystemR410A, Cooling Only/Heat PumpAMNC076LQL0 AMNC096AP*1AMNC096LQL0 AMNC126AP*1AMNC126

Page 5

12 MPS Variable Multi Split System(50Hz, R410A)1. Power SupplyType Outdoor Unit Power SupplyCooling Only1Ø, 220~240V, 50HzHeat PumpNote : Power Supply

Page 6 - Features

2004 Product Data 132. Model Number Nomenclature2.1 Indoor Units2.2 Outdoor UnitsAMN H 607QL L 0Chassis NameSerial NumberCombination of FunctionsAR

Page 7

14 MPS Variable Multi Split System(50Hz, R410A)3. Outline of SystemThe system has number of indoor units attached to an outdoor unit which saves energ

Page 8 - Auto Cleaning System :

2004 Product Data 153. Outline of System3.3 External Appearance of Indoor UnitsWall MountedAMNC076LQL0 AMNH076LQL0 AMNC096LQL0 AMNH096LQL0AMNC126

Page 9 - Thinnest Turbo Fan

16 MPS Variable Multi Split System(50Hz, R410A)4. List of FunctionsModelFeaturesAirflow Direction Control(Left & Right) Manual Manual Manual Manua

Page 10 - Features & Benefit

2004 Product Data 175. Specifications1764(2051) 2267(2638) 3024(3515 4536(5275) 5795(67407000 9000 12000 18000 23000 ----------5.5(194) 6.0.(212) 9

Page 11

18 MPS Variable Multi Split System(50Hz, R410A)5. SpecificationsHeat PumpNominal Cooling Capacity ★ kcal/hr(W)Btu/hrNominal Heating Capacity ★ kcal/hr

Page 12 - R410A, Cooling Only/Heat Pump

2004 Product Data 1General DescriptionThank you very much for your special patronage of LG air-conditioners.A high-grade, high-quality, advanced in

Page 13 - External wiring procedure

2004 Product Data 195. SpecificationsNotes: 1. Capacities are based on the following conditions:Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C

Page 14 - 2.2 Outdoor Units

20 MPS Variable Multi Split System(50Hz, R410A)5. SpecificationsNotes: 1. Capacities are based on the following conditions:Cooling: - Indoor Temperatu

Page 15 - 3. Outline of System

2004 Product Data 216. Combination TableCooling6.1 Cooling Only6.1.1 A2UC146FA0Combination(k Btu)Capacity (Btu/h)CoolingInput(W)Current(A)EER(Btu/h

Page 16

Cooling6.1.4 A4UC306FA022 MPS Variable Multi Split System(50Hz, R410A)6. Combination TableCombination(k Btu)Capacity (Btu/h)CoolingUnit-A Unit-B Unit-

Page 17 - Optional : Factory-Installed

2004 Product Data 236. Combination TableCoolingHeatingHeating6.2 Heat Pump6.2.1 A2UH146FA0Combination(k Btu)Capacity (Btu/h)CoolingUnit-A Unit-B Un

Page 18 - Cooling Only

24 MPS Variable Multi Split System(50Hz, R410A)6. Combination TableCooling6.2.3 A3UH216FA0 HeatingCombination(k Btu)Capacity (Btu/h)CoolingUnit-A Unit

Page 19 - Heat Pump

2004 Product Data 256. Combination TableCooling6.2.4 A4UH306FA0 Combination(k Btu)Capacity (Btu/h)CoolingUnit-A Unit-B Unit-C Unit-D TotalInput(W)C

Page 20 - 5.2 Outdoor Units

26 MPS Variable Multi Split System(50Hz, R410A)6. Combination TableHeatingCombination(k Btu)Capacity (Btu/h)HeatingUnit-A Unit-B Unit-C Unit-D TotalIn

Page 21

2004 Product Data 277. Dimensional DrawingsAMNC-LQ/LR/LT, AMNH-LQ/LR/LTW8249001090H260285314D155156172ModelAMNC/H076LQL0AMNC/H096LQL0AMNC/H126LRL0A

Page 22 - 6.1 Cooling Only

28 MPS Variable Multi Split System(50Hz, R410A)W570H568D129ModelAMNC/H096AP*1AMNC/H126AP*1(unit : mm)7. Dimensional DrawingsØ 9.52Ø 6.359, 12kGasLiqui

Page 23 - 6.1.4 A4UC306FA0

2 MPS Variable Multi Split System(50Hz, R410A)

Page 24 - 6.2 Heat Pump

2004 Product Data 297. Dimensional DrawingsA2UC146FA0, A2UH146FA07.2 Outdoor UnitsWL6L7 L8 L9L4HDL1L2L3L5L10Gas side3-way valveLiquid side2-way val

Page 25 - 6.2.3 A3UH216FA0

30 MPS Variable Multi Split System(50Hz, R410A)7. Dimensional DrawingsA2UC186FA0, A2UH186FA0WDL1L2L9L4L3HL10L10L10L8Gas side3-Way valveLiquid side2-Wa

Page 26 - 6.2.4 A4UH306FA0

2004 Product Data 317. Dimensional DrawingsA3UC216FA0, A3UH216FA0WL5L6 L7 L8L3HDL1L2L4L10L9Gas side3-way valveLiquid side2-way valveL10L10L10L10W m

Page 27

32 MPS Variable Multi Split System(50Hz, R410A)7. Dimensional DrawingsA4UC306FA0, A4UH306FA076.54-holes for anchor bolts50505050505032064160160 550106

Page 28 - 7.1 Indoor Units

2004 Product Data 338. Wiring Diagrams3854A20135WCN-TH1THERMISTOR(OUT-PIPE)THERMISTOR(IN-PIPE)THERMISTOR(ROOM)CN-TH2CN-U/DCN-MOTORCN-POWERAC PCB AS

Page 29 - AMNC-AP, AMNH-AP

34 MPS Variable Multi Split System(50Hz, R410A)8. Wiring DiagramsART COOL TypeCONNECT PCB ASMDISPLAYPCB ASMAC PWB ASM DC PWB ASMCN-UD(BL)CN-LR1(WH)CN-

Page 30 - 7. Dimensional Drawings

2004 Product Data 358. Wiring DiagramsA2UC146FA08.2 Outdoor UnitNotes: BL BLUE BK BLACK BR BROWNRD RED OR ORANGE WH WHITEYL YELLOW GN/YL GREEN/YELL

Page 31

36 MPS Variable Multi Split System(50Hz, R410A)8. Wiring DiagramsA2UC186FA0OUTDOOR WIRING DIAGRAMTMTB1OLPOLPBLBLBLBRBRBRBLORYL1(L)2(N)33MAIN PWB ASSYC

Page 32

2004 Product Data 378. Wiring DiagramsA3UC216FA0OUTDOOR WIRING DIAGRAMTB1BLBLBLBRBRORYLRDBRBLMAIN PWB ASSYP/NO : 3854A20392BTMGN/YL1(L)2(N)3332(N)2

Page 33

38 MPS Variable Multi Split System(50Hz, R410A)8. Wiring DiagramsA4UC306FA0OUTDOOR WIRING DIAGRAMTM32(N)1(L)332(N)2(N)1(L)1(L)3TB1BLBLBLBRBRORYLRDWHBR

Page 34 - 8. Wiring Diagrams

2004 Product Data 3LG Airconditioners Product DataTABLE OF CONTENTSTable of contents PagePart 1 Features...

Page 35

2004 Product Data 398. Wiring DiagramsA2UH146FA0OUTDOOR WIRING DIAGRAMMAINPOWERAS/VCMFMoP/NO : 3854A20375ABS/VB/PS/V4WVMAIN PCB ASSYBKBKBKBRBKBKT/B

Page 36 - RD RED OR ORANGE WH WHITE

40 MPS Variable Multi Split System(50Hz, R410A)8. Wiring DiagramsA2UH186FA0OUTDOOR WIRING DIAGRAMTB1TB2OLPOLPBRBLBLBL BRBL BRORYLMAIN PWB ASSYCN-COM(W

Page 37

2004 Product Data 418. Wiring DiagramsA3UH216FA0OUTDOOR WIRING DIAGRAMBLMAIN PWB ASSY4WVP/NO : 3854A20216UCN-LEV2(BL)CN-LEV3(YL)LEVBLEVCLEVACN-LEV1

Page 38

42 MPS Variable Multi Split System(50Hz, R410A)8. Wiring DiagramsA4UH306FA0OUTDOOR WIRING DIAGRAMCN-COM(WH)CN-POWER(WH)CN-TH1FUSET3.15APIPE TEMPSENSOR

Page 39

2004 Product Data 439. Piping DiagramsHeat ExchangerC.F.Flndoor unit:Cooling: ThermistorGasØ9.52(3/8)Ø12.7(1/2)LiquidØ6.35(1/4)ModelAMNC076LQL0AMNC

Page 40

44 MPS Variable Multi Split System(50Hz, R410A)9. Piping DiagramsHeat ExchangerC.F.Flndoor unit:Cooling: Thermistor:Heating[unit:mm(inch)]Refrigerant

Page 41

2004 Product Data 459. Piping DiagramsRoom BAccumulatorCompressorHeatExchangerHeaderRoom ARoom BRoom AOUTDOOR UNITField PipingGasField PipingLiquid

Page 42

46 MPS Variable Multi Split System(50Hz, R410A)9. Piping DiagramsLEV-ALEV-BLEV-CHeaderRoom CRoom AField PipingLiquidRoom BRoom CRoom AField PipingGasR

Page 43

2004 Product Data 479. Piping DiagramsRoom BAccumulatorCompressorHeatExchangerHeaderRoom AOUTDOOR UNITField PipingGasReversingValveRefrigerant Flow

Page 44 - : Thermistor

48 MPS Variable Multi Split System(50Hz, R410A)9. Piping DiagramsAccumulatorLowPressureHeatExchangerCheckValve(2)CheckValve(1)ReversingValveOUTDOOR UN

Page 45

4 MPS Variable Multi Split System(50Hz, R410A)

Page 46 - OUTDOOR UNIT

2004 Product Data 4910. Capacity Table10.1 A2UC146FA0[Cooling Capacity]10.2 A2UC186FA0[Cooling Capacity]TC PI TC PI TC PI TC PI TC PI TC PIkW kW kW

Page 47

50 MPS Variable Multi Split System(50Hz, R410A)10. Capacity Table10.3 A3UC216FA0[Cooling Capacity]TC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW

Page 48

2004 Product Data 5110. Capacity Table10.4 A4UC306FA0[Cooling Capacity]TC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombin

Page 49 - 9. Piping Diagrams

52 MPS Variable Multi Split System(50Hz, R410A)10. Capacity TableTC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombinationCapa

Page 50 - Cooling Only

2004 Product Data 5310. Capacity TableTC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombinationCapacity Index(kBtu/h)Outdoo

Page 51 - 10.3 A3UC216FA0

54 MPS Variable Multi Split System(50Hz, R410A)10. Capacity Table10.5 A2UH146FA0[Cooling Capacity][Heating Capacity]TC PI TC PI TC PI TC PI TC PI TC P

Page 52 - 10. Capacity Table

2004 Product Data 5510. Capacity Table10.6 A2UH186FA0[Cooling Capacity]Heat PumpTC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW

Page 53

56 MPS Variable Multi Split System(50Hz, R410A)10. Capacity Table[Heating Capacity]TC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW

Page 54

2004 Product Data 5710. Capacity TableHeat Pump10.7 A3UH216FA0[Cooling Capacity]TC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW

Page 55 - [Heating Capacity]

58 MPS Variable Multi Split System(50Hz, R410A)10. Capacity Table[Heating Capacity]TC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW

Page 56 - 10.6 A2UH186FA0

2004 Product Data 5Part 1Features

Page 57

2004 Product Data 5910. Capacity Table10.8 A4UH306FA0[Cooling Capacity]TC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombin

Page 58 - 10.7 A3UH216FA0

60 MPS Variable Multi Split System(50Hz, R410A)10. Capacity TableTC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombinationCapa

Page 59

2004 Product Data 6110. Capacity TableTC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombinationCapacity Index(kBtu/h)Outdoo

Page 60

62 MPS Variable Multi Split System(50Hz, R410A)10. Capacity TableTC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombinationCapa

Page 61

2004 Product Data 6310. Capacity TableHeat PumpTC PI TC PI TC PI TC PI TC PI TC PIkW kW kW kW kW kW kW kW kW kW kW kWCombinationCapacity Index(kBtu

Page 62

64 MPS Variable Multi Split System(50Hz, R410A)11. Operation LimitsItem RangeInlet air temperature(Cooling)Inlet air temperature(Heating)Power source

Page 63

2004 Product Data 6512. Air Velocity and Temperature Distributions(Reference Data)7k Btu/h Model12.2 ART COOL Type12k Btu/h ModelAir velocity [m/s]

Page 64

66 MPS Variable Multi Split System(50Hz, R410A)13. Sound LevelsOverallSound Pressure LevelAMNC/H076LQL0 AMNC/H096LQL0 AMNC/H126LRL0 AMNC/H186LTL0 AMNC

Page 65 - 10(50) 24(75.2)

2004 Product Data 67ART COOL13. Sound LevelsOverallSound Pressure LevelAMNC/H096AP*1 AMNC/H126AP*1Notes:- Sound measured at 1m away from the cen

Page 66 - 12.1 Wall Mounted Type

68 MPS Variable Multi Split System(50Hz, R410A)13. Sound Levels13.2 Outdoor UnitOverallSound Pressure LevelA2UC/H146FA0 A2UC/H186FA0 A3UC/H216FA0A4UC/

Page 67 - 13. Sound Levels

6 MPS Variable Multi Split System(50Hz, R410A)Features & BenefitMPS(Multi Power System) Variable Control : (Except A2UC146FA0,A2UH146FA0)Big Energ

Page 68

2004 Product Data 6914. Installation14.1 Piping Length & Refrigerant ChargeThe maximun allowable level and piping length7.5mIt does not matter

Page 69 - Sound Pressure Level

70 MPS Variable Multi Split System(50Hz, R410A)14. Installation• There should not be any heat source or steam nearthe unit.• There should not be any o

Page 70 - Refrigerant Charge

2004 Product Data 7114. Installation14.2.2 Outdoor Unit• If an awning or canopy is built over the unit to prevent direct sunlight or rain exposure,

Page 71 - 14. Installation

72 MPS Variable Multi Split System(50Hz, R410A)14. Installation14.4 Connecting Pipings and the cable to Outdoor unit14.4.1 Connecting the pipings to t

Page 72

2004 Product Data 7314. InstallationConnecting the cable to the Outdoor unit.CAUTION: Provide a circuit breakerbetween power source and the unit as

Page 73 - 14.4.2 Connect the cable

74 MPS Variable Multi Split System(50Hz, R410A)14. InstallationCAUTIONAfter the confirmation of the above conditions, prepare the wiring as follows.1.

Page 74 - 2004 Product Data 73

2004 Product Data 7514. Installation14.5 Drain Pipe Work❑ Drain pipe gradient and support 1) - The drain pipe must be fitted at a gradient of at le

Page 75

76 MPS Variable Multi Split System(50Hz, R410A)15. Function of Remote ControllerONOFFCANCELAUTO CLEANSET135491017181672813141511612Cooling OperationAu

Page 76 - H: 50mm or more

P/No.: 3828A20428F 20 Yoido-dong, Youngdungpo-gu, Yoido P.O.Box 355Seoul 150-721, KoreaPhone: 3777-7969 Fax: 3777-5137/8http://www.lge.comhttp://biz.

Page 77 - Operation Mode

2004 Product Data 7Features & Benefit90(Min)0100200300400500(ppm)6030Nano Filter++++++++++++++++Normal FilterAir Purifying System- It not only

Page 78 - P/No.: 3828A20428F

8 MPS Variable Multi Split System(50Hz, R410A)Features & BenefitVertical TemperatureDifferenceHorizontal TemperatureDifferenceImproved value of th